รายละเอียดสินค้า
250 hp - 125 PSIG - Hot Water - Ultra Low NOx Nationwide Boiler’s 250 hp (8.4 mmbtu ouput) skid-mounted Cleaver-Brooks model CBLE 700-250-125 hydronic heating firetube boiler is designed at 125 psig pressure, firing natural gas. It was built in 2010, is fully piped and wired and includes the following components.
- 250 HP Cleaver Brooks 4-pass Dryback Firetube Boiler .
- FD Fan with 10 HP Motor & Fused Starter.
- Low NOx Natural Gas Firing.
- CB7800 Burner Management System with Expanded Annunciator.
- Honeywell UDC2500 Controller.
- Servo Motor Parallel Positioning Combustion Control.
- NEMA 12 Panel.
- 480v - 115v Control Voltage Transformer.
- Dual Low Water Cut Offs.
- Pressure/Temperature Gauges.
- Safety Relief Valves.
- Drain Valves.
- Meets FM/IRI Insurance, CSD-1 and California Code Requirements.
- Bell & Gossett Size 1510 Circulating Pump, Base Mounted Connected to a 10 HP TEFC, 1800 rpm Motor - Shipped Loose (800 gpm @ 30 TDH).
- O&M Manuals with Drawings.
Fuel Consumption
Natural Gas |
10,460 SCFH @ 3-10 psig |
Connection Sizes
Hot Water Supply |
8"-150# FLG |
Hot Water Return |
8"-125# FLG |
Natural Gas |
2" NPT |
Drain |
2" NPT |
Electrical Power Service Requirements
480 VAC, 3 ph, 60 hz, 50 AMPS |
Dimensions & Weights
Length |
15' 11" |
Width |
7' 11" |
Height |
9' 7" |
Shipping Weight |
21,700 lbs |
Operating Weight |
35,580 lbs |
Emissions Data (natural gas)
NOx (corr. to 3% O2) |
30 ppm |
CO (corr. to 3% O2) |
50 ppm |