รายละเอียดสินค้า
650 HP - 250 PSIG Ultra Low NOx Nationwide Boiler’s ultra low NOx, 650 hp (22,500 lbs/hr) skid mounted boiler is designed at 250 psig pressure, firing natural gas. It is fully piped and wired and includes the following components.
- 650 hp Package Firetube Boiler.
- Ultra Low NOx Burner.
- Gas Pressure Regulator.
- Control Panel (Honeywell 7800 Series).
- Forced Draft Fan & Motor.
- Complete Gas Train.
- Steam Pressure Gauge.
- Low Water Cutoffs.
- Water Column & Site Glass.
- Safety Valves.
- Feedwater Stop & Check Valves.
- Modulating Feedwater Control Valve.
- Bottom Blowdown Valves.
- Continuous Blowdown Metering Valve.
- High/Low Water & Flame Failure Alarm.
- Pilot System w/ Electric Ignition.
- Stack (loose).
- Meets FM / IRI / NFPA 85.
- Operating Manuals.
Fuel Consumption
Natural Gas |
27,200 SCFH @ 8-15 psig reg. |
Connection Sizes
Main Steam |
6"-250# FLG (valve outlet) |
Natural Gas |
2½"-150# FLG |
Blowdown / Drain |
2" NPT |
Feedwate |
2" NPT |
Instrument Air |
½" NPT |
Electrical Power Service Requirements
460 VAC, 3 ph, 60 hz, 100 AMPS |
Dimensions & Weights
Length |
28' 10" |
Width |
8' 6" |
Height |
9' 3" |
Shipping Weight |
36,000 lbs |
Operating Weight |
50,000 lbs |
Emissions Data (natural gas)
NOx (corr. to 3% O2) |
9 ppm |
CO (corr. to 3% O2) |
50 ppm |