In conjunction with the appropriate IGEMA level probes the LMC2 low water level limiter is a limiter in accordance with the Pressure Equipment Directive (PED). The product meets EU Directive 2014/68/EU (PED). Regulations applied: corresponding DIN EN standards. Due to a self-test, the limiter ensures the safety function. Thus he can be implemented in systems with safety requirements up to SIL 3.
PED-Standard | DIN EN 12952-11 : 2007; DIN EN 12953-9 : 2007 |
Safety intefrity level | SIL 3 EN61508 : 2010 ; EN12952-11 : 2007 5.5; EN 12953-9 : 2007 5.5 |
Electromagnetic Compatibility | EN 61326-1 : 2006 |
Low Voltage | EN 61010-1 : 2010 |
Mains Connection | 230 V (-15% + 10%) /50/60Hz |
Power Consumption | 3 VA |
Hardware Protection | short-circuit-proof transformer |
Protection Class (DIN EN 60529) | IP40 |
Ambient temperature | 0 °C - 55 °C |
Self Monitoring | Every 2 s |
Burner cut-off | Voltage | Max. 250 Vac |
Current | Max. 6 A ohmsch | |
Auxiliary relay | Voltage | Max. 250 Vac |
Current | Max. 5 A ohmsch | |
Electrical conductivity of the liquid | 0,5 μs/cm ≤ æ ≤ 10.000 μS/cm (25 °C) | |
Length of connection line | Max. 100 m |
6/5 หมู่ 10 ถนนเพชรหึงษ์ ตำบลบางยอ อำเภอพระประแดง จังหวัดสมุทรปราการ 10130
เบอร์โรงงาน : (66) 02-084-7984 , 02-100-4954 ฝ่ายบัญชี : 02-004-0773 ฝ่ายขาย : 094-990-2334 แฟกซ์ : 02-100-4908 line id: @service1977 อีเมล์ : sales@steamfilter.co.th